US
Metric

Overview

The range of Olympian™ generator sets provides reliable energy solutions for every business, every need. Olympian generators can be installed as the prime power source or standby service. They deliver dependable, clean, economical power – even in the most demanding conditions – and are available in a wide range of configurations with optional equipment.

Generator Set Specifications

Standby
50 hz: 88.0 kW (110.0 kVA) 60hz: 100.0 kW (125.0 kVA)
Prime
50 hz: 80.0 kW (100.0 kVA) 60hz: 90.4 kW (113.0 kVA)
Voltage
380/220 to 220/127 Volts
Frequency
50 or 60 Hz
Speed
1500 or 1800 RPM
Emissions/Fuel Strategy
EU Stage II

Engine Specifications

Engine Model
Perkins™ 1104C-44TAG2
Compression Ratio
18.3:1
Aspiration
TA
Governor Type
Electronic
Bore
4.10 in
105.00 mm
Displacement
268.50 in³
4.40 B
Stroke
5.00 in
127.00 mm
Recommended Fuel
Class A2 Diesel or BSEN590