What service should I do weekly on my genset?
This depends somewhat on the application of your genset (Prime or Standby) but typical daily and weekly services include:
Prime Power | |||||
---|---|---|---|---|---|
Daily | Weekly | ||||
Control Panel check Coolant Level check Air cleaner service indicator check Oil level check Drain fuel/water separator Drain fuel tank water and sediment Test/Record Generator bearing temperatures Generator Load Check Power Factor Check Walk Around inspection |
Automatic start/stop inspection Battery Charger check Electrical Connections check Generator Inspection Generator Leads check Space heater test Stator Winding temperature check Voltage and Frequency Check |
Standby Power | |||||
---|---|---|---|---|---|
Daily | Weekly | ||||
Control Panel check Coolant Level check Oil level check Generator Load Check- if running/testing Power Factor Check- if running/testing Walk Around inspection |
Automatic start/stop inspection Battery Charger check Battery Electrolyte level check Electrical Connections check Air cleaner service indicator check Drain fuel/water separator Drain fuel tank water and sediment Test/Record Generator bearing temperatures Space heater test Stator Winding temperature check Voltage and Frequency Check |